ShipCalculators.com

HFC-227ea Quantity (FM-200)

FM-200 / HFC-227ea agent quantity for total flooding from FSS Code Ch.5: 6.25–9 % v/v concentration.

Fire safetyGaseous
Loading calculator…

Formula, assumptions, and limits

W=VC/100s(1C/100),s=0.1269+0.000513TW = \frac{V \cdot C / 100}{s \cdot (1 - C/100)}, \quad s = 0.1269 + 0.000513 T
SymbolMeaningUnit
VVProtected volume
CCDesign concentration% v/v
ssSpecific vapour volume of HFC-227ea at Tm³/kg
WWAgent masskg

Source: FSS Code Ch.5; NFPA 2001 - Clean Agent Fire Extinguishing Systems

In short

FM-200 / HFC-227ea agent quantity for total flooding from FSS Code Ch.

Learn the theory FSS Code: International Code for Fire Safety Systems